with Purchase of Furnace & AC
Includes Merv 16 5" media cabinent and ApcoX Premium UV-light. Cannot be combined with any other offers. Must present coupon at time of service. Not valid on previously completed work.
To get assistance with your HVAC and plumbing repairs, maintenance, and installations, look no further! To see what our satisfied customers think about our HVAC and plumber services in Prescott, WI, read our reviews below.
Responded to no-cool call on 5-year-old air conditioning system. Upon arrival, found unit was cooling but experiencing water leakage from evaporator coil drain line. Diagnosed plugged condensate drain causing water backup and overflow onto floor. Cleared blockage from drain line and restored proper drainage flow. Performed comprehensive system inspection of indoor air handler. Evaporator coil condition satisfactory with no signs of freezing or damage. Air filter clean and within acceptable service parameters. Checked all accessible ductwork connections for proper sealing. Inspected outdoor condensing unit and found coil heavily contaminated with dirt and debris restricting airflow. Removed access panels and performed thorough cleaning of condenser coil fins to restore heat transfer efficiency. Cleaned exterior cabinet and surrounding area of accumulated debris. Conducted electrical system diagnostics. Tested capacitor for proper microfarad rating and verified within manufacturer spe
Responded to a no cooling call on a 7-year-old AC system. Upon arrival, inspected the outdoor unit and found the condenser coils dirty; cleaned thoroughly. Verified contactor and capacitor were operating normally with proper 240V power supply to the outdoor unit. Traced power issue to the indoor furnace where no 120V was present. Located tripped breaker at electrical panel, reset breaker, and restored power to the system. Tested system operation and confirmed unit running properly. Performed refrigerant pressure readings which were within manufacturer specifications. Recommended follow-up electrical inspection to determine root cause of breaker trip and prevent future occurrences.
Responded to service call for 9-year-old AC system experiencing high humidity issues while still providing cooling. Upon arrival, performed initial diagnostics and measured a 15° temperature split across the evaporator coil. Inspected air filter, which was found to be clean. Observed standing water between furnace and drain line, indicating potential drainage restriction. Flushed and cleared evaporator drain line to restore proper condensate removal. Proceeded to outdoor unit for comprehensive inspection of electrical components, confirming all connections and controls were functioning within normal parameters. Identified dirty condenser coil and performed thorough coil cleaning to restore optimal heat transfer efficiency. Verified blower motor speeds and airflow characteristics were operating correctly. Connected manifold gauges to measure refrigerant pressures and temperatures. Diagnostics revealed system was operating with insufficient refrigerant charge, which explained the exces
Responded to service call for kitchen sink backing up due to deep clog in drain line. Upon arrival, determined that previous cabling attempts by homeowner had been unsuccessful in clearing the obstruction. Diagnostic assessment indicated grease buildup as the primary cause of the blockage. Cabled the entire kitchen drain line from the sink basin through to the mainline connection, successfully removing all debris and grease accumulation from the pipe. Utilized drain camera to verify complete clearance of the line and confirm proper flow throughout the entire drain system. Conducted thorough operational testing by filling and draining both basins of the double-sink multiple times to ensure proper drainage and flow rate. Inspected all connections and verified no leaks were present in the system. Kitchen sink restored to full working condition with clear drainage confirmed.
Performed complimentary estimate for washing machine drain line reconfiguration. Customer requested disconnection from existing cast iron drain system and reconnection to new PVC piping. Conducted camera inspection of existing drain line to assess conditions and determine scope of work required. Camera inspection revealed that the existing cast iron drain is open and functional, but the 1¼" copper drain line serving the washing machine is suspected to be obstructed with lint accumulation. Attempted to navigate camera through cast iron system approximately 40 feet to connection point where clothes washer ties in, but encountered difficulty due to T-fitting orientation causing camera to fold back on itself. Inspection identified two separate penetrations through block wall foundation for sewer connections. System consists of mixed materials including PVC on one side of basement and 4" cast iron on opposite side, with only the clothes washer currently tied into the cast iron section. Ob
Responded to no cool complaint on 10-year-old system experiencing short cycling at condenser. Upon arrival, system was operating but outdoor unit was severely plugged with debris, causing unit to overheat and shut down on high-temperature days. Verified all electrical components, capacitors, and compressor diagnostics were within normal operating specifications. Performed complete tune-up service including thorough cleaning of condenser coil to remove accumulated debris and restore proper airflow. Explained to customer that inadequate airflow from dirty coil was causing thermal overload protection to trip during peak cooling demand. System tested successfully after service with proper temperatures and run times. Discussed benefits of regular preventative maintenance program to prevent future occurrences. Unit restored to proper cooling operation.
Responded to service call for non-functional outdoor faucet and secondary water meter cap-off request. Upon inspection, discovered the silcock stem had broken off inside the valve body, making repair impossible. Removed the failed silcock unit and installed a complete replacement fixture. Additionally, capped off the secondary water meter as requested and provided required sign-off documentation for the meter closure.
Completed comprehensive plumbing inspection of residential property, including evaluation of outdoor spigot for wear as requested and interior toilet tank components. Documented toilet fill valve assembly with blue float mechanism, flush valve with flapper, and braided supply line connections, noting water staining in tank and moisture damage on surrounding wooden surfaces. All plumbing fixtures were inspected and photographed for maintenance records.
Responded to no cooling complaint on 22-year-old R22 air conditioning system. Upon inspection, found failed capacitor with evidence of previous replacement. Replaced capacitor and tested system operation. Post-repair diagnostics revealed compressor drawing excessive amperage beyond maximum rated specifications and high-side refrigerant pressure exceeding 250 psi (normal range 150-180 psi), indicating compressor failure and system restriction. Advised customer that capacitor replacement is temporary measure without guarantee due to underlying compressor failure. Explained risk of indoor coil freezing and potential water damage to furnace. System contains obsolete R22 refrigerant. Recommended complete system replacement and scheduled estimate appointment.
Responded to no-cooling complaint on 2-year-old Goodman air conditioning system that would not restart after cycling off. Upon arrival, found thermostat set to 66 degrees with system not running and no error codes displayed. Performed diagnostic testing including amp draw measurements on compressor, verified capacitor functionality, and inspected control board and electrical connections. All electrical components tested within normal operating parameters with no mechanical or electrical failures identified. Determined system was likely experiencing thermal overload protection lockout due to excessive runtime attempting to maintain unrealistic setpoint during high ambient temperature conditions. Advised proper thermostat settings around 70 degrees to prevent system from overworking and cycling on thermal protection, which would explain intermittent operation requiring breaker resets to restore functionality.
Performed preventative maintenance inspection on two 5-6 year old air conditioning systems as part of routine tune-up agreement. Conducted comprehensive evaluation of both units including cleanliness assessment, efficiency testing, and reliability checks. Testing revealed low capacitor readings on system requiring immediate replacement to prevent compressor failure. Replaced defective capacitor and verified proper system operation. Both units now operating within manufacturer specifications and ready for cooling season.
Completed comprehensive 8-12 point air conditioning tune-up on 3-year-old FRP system. Performed standard maintenance inspection and testing protocol, verifying all components are operating within manufacturer specifications. System confirmed to be functioning as designed with no adjustments or repairs necessary at this time.
Responded to service call for toilet flush valve replacement. Upon arrival, assessed existing flush valve system and determined standard diameter valve and gaskets were required. Attempted installation of replacement flush valve mechanism; however, during rebuild process discovered the parts provided were incompatible with the existing toilet fixture. Documented the incorrect components with comparison photos showing the old deteriorated flush valve alongside the new unit to verify dimensional and mounting discrepancies. Additional parts with correct specifications will be required to complete the flush valve replacement and restore proper toilet function.
Responded to service call for leaking temperature and pressure relief valve on tanked water heater and clogged kitchen sink drain. Upon inspection, discovered the T&P valve was dripping and required replacement. Additionally, identified a cracked 3-inch PVC 90-degree elbow fitting on the water heater vent pipe that posed a potential safety hazard. Snaked the kitchen drain to clear the obstruction and restore proper drainage. Replaced the faulty T&P relief valve and installed new 3-inch PVC 90-degree elbow on the vent system above the water heater to ensure proper venting and code compliance.
Responded to a recurring dishwasher drainage issue that had been previously addressed. Upon inspection, tested the dishwasher by running it into the sink, which drained properly, indicating the unit itself was functioning correctly. Reassembled the dishwasher drain connection to the standpipe, ensuring proper positioning and depth to prevent blockage. Performed three complete fill and drain cycles to verify proper operation and confirm the issue was resolved.
Responded to a standby call for a clogged hand wash sink at a commercial facility. Upon arrival, assessed the stainless steel sink and determined the drain line was obstructed. Successfully snaked the drain line to clear the blockage and restore proper drainage function.
Completed comprehensive AC tune-up and discovered mouse nest in low voltage wiring causing system issues. Removed nest debris, repaired damaged low voltage wiring connections, and restored proper electrical functionality. Verified system operation and ensured all components were functioning correctly after repairs.
Completed warranty callback on Revolv furnace unit. Successfully replaced front door nameplate with correct manufacturer branding. Door latch replacement could not be completed due to incorrect part received; submitted new part request for proper latch component to complete warranty repair.
Responded to no cooling complaint on 9-year-old residential air conditioning system experiencing evaporator coil freeze-up after 20 minutes of operation. Upon arrival, confirmed system was low on refrigerant and verified outdoor condenser coil was clean with adequate airflow. Performed electrical diagnostics using multimeter to test system components and verify proper voltage. Documented outdoor unit condition and internal electrical measurements. System requires refrigerant charge and leak detection to restore proper cooling operation; presented repair options to address refrigerant loss and restore system functionality.
Responded to service call for continuously running toilet in unit 12-4. Upon inspection, found flush tower mechanism experiencing operational failure due to excessive iron content in water supply causing mineral buildup and interference. Tank interior exhibited significant rust-colored staining and discoloration throughout, with brownish water present indicating high iron concentration. Flush valve assembly components showing signs of binding and improper operation from accumulated mineral deposits. Diagnosed that internal flush mechanism requires complete replacement due to deterioration from poor water quality conditions. Provided estimate for replacement of all internal tank components to restore proper toilet function and eliminate continuous running condition.
©2026 Hurlburt. All Rights Reserved.
Privacy Policy | Terms and
Conditions
This site is protected by reCAPTCHA and the Google Privacy Policy and Google Terms of Service apply.