Responded to leaking water heater fittings on an AO Smith ProLine XL unit previously installed. Upon inspection, found active leaks at two top-mounted pipe connections with visible corrosion and rust staining on tank surface and drain pan. Due to ongoing water quality issues that have caused repeated service calls and equipment damage, repair work has been postponed pending water treatment evaluation and recommendations to address the root cause before proceeding with fitting repairs or replacements.
Responded to no cooling complaint on geothermal heat pump system. Upon arrival, found thermostat water temperature control incorrectly set to heating mode instead of cooling mode, preventing system from operating. Corrected thermostat settings and cycled unit multiple times to verify proper operation. Performed complete cooling season tune-up and maintenance inspection per rewards membership agreement. Checked refrigerant pressures and temperature differentials on geothermal unit - all readings within manufacturer specifications. Inspected air handler, ductwork connections, and associated components. System tested and left in proper working order with cooling function restored.
Completed scheduled furnace tune-up on 4-year-old Lennox gas furnace system. Replaced dirty air filter, performed comprehensive inspection of gas valve assembly, burner components, and electrical control system. All components found to be operating within normal parameters; customer advised that comfort advisor will follow up regarding air conditioning installation options.
Performed comprehensive tune-up on both air conditioning and furnace systems. Completed full inspection and maintenance procedures on outdoor condenser unit and indoor heating equipment, verifying proper operation of all components. Replaced air filter with customer-provided filter, and confirmed both systems are functioning within normal parameters.
Responded to callback regarding shower valve cartridge installation and water line testing concerns. Installed shower valve cartridge and completed plumbing rough-in work with PVC supply lines properly secured to wooden blocking between wall studs using appropriate clamps and straps. Configured water supply lines in U-shaped loop configuration to accommodate valve placement. All plumbing lines properly supported and ready for pressure testing per code requirements.
Completed installation of Moen shower valve and drain assembly in bathroom renovation area. Installed rough plumbing components including vertical PVC drain lines secured to horizontal backing boards with proper fasteners. Set shower drain fitting with gasket in fiberglass shower basin and connected to drainage system. All plumbing rough-in work completed per manufacturer specifications and ready for wall finishing and trim-out phase.
Completed annual AC tune-up on 3-year-old Lennox system as part of maintenance agreement. Performed comprehensive inspection of outdoor condenser unit and indoor air handler, cleaned components, and verified all equipment operating within normal parameters. Resolved thermostat connectivity issue by migrating customer from discontinued Lennox S30 app to updated S40 app platform, restoring full remote control functionality.
Responded to no heat call and found furnace would not ignite due to failed gas valve. Removed defective gas valve that had been installed two years prior and installed new replacement gas valve. Performed complete leak check on all gas connections to ensure system safety. Fired up furnace and verified proper ignition sequence and operation throughout complete heating cycle.
Performed comprehensive preventative maintenance tune-up on central air conditioning system. Inspected and confirmed air filter, blower assembly, and evaporator coil were clean and in proper condition. Discovered missing drain plug on condensate pan causing overflow condition with minimal water accumulation. Cleared and verified condensate drain line was functioning properly. Conducted electrical inspection on outdoor condensing unit, confirming all components operating within manufacturer specifications. Tested system operation with 15-minute runtime, achieving 18-20 degree temperature differential indicating proper refrigerant charge and heat exchange. Installed replacement drain plug on evaporator pan, resolving leak issue. System operating efficiently with no further concerns noted.
Completed scheduled tune-up and maintenance on 2-year-old Generac residential standby generator. Upon arrival, found unit displaying error code 2800 indicating auxiliary shutoff switch had been activated. Diagnosed that external shutoff switch on backside of unit had been inadvertently flipped, causing offline status and triggering maintenance alert emails. Reset auxiliary switch and cleared error code from system. Performed complete maintenance service including oil change, spark plug replacement, air filter replacement, and oil filter replacement. Reset maintenance notification timer and restored unit to full operational status. Provided customer education on location of external shutoff switches and demonstrated proper reset procedure to prevent future accidental activation.
Completed comprehensive AC tune-up maintenance with no pre-existing issues reported. Cleaned condenser coil, inspected electrical connections confirming proper operation, replaced air filter, and cleared condensate drain line. System operating efficiently with 18-degree temperature differential across evaporator coil, indicating proper refrigerant charge and airflow.
Responded to no cooling complaint on residential air conditioning system. Upon arrival, found indoor temperature in mid-80s with system running but struggling to achieve setpoint of 73°F after extended period of being off during occupant vacation. Performed comprehensive system evaluation including visual inspection of indoor and outdoor equipment. Verified air filter was clean and recently replaced. Inspected outdoor condensing unit and confirmed coil was clean with no visible obstructions. Utilized FLIR thermal imaging camera to measure supply and return air temperatures, confirming approximately 22°F temperature split across evaporator coil, indicating refrigeration circuit was operating within normal parameters and producing adequate cooling capacity. Conducted thorough airflow assessment throughout occupied space. Identified primary issue as severely restricted airflow due to multiple supply grilles and return air openings blocked by household items and belongings. Restricted air
Responded to service call for Lennox multi-zone heat pump system with two indoor mini-split heads experiencing operational issues. Lower unit displayed P6 error code but continued to provide cooling; upper unit ran but discharged warm air instead of conditioned air. Performed system reset and monitored operation for approximately one hour. Consulted with manufacturer technical support regarding intermittent P6 code and warm air discharge from upper head. Technical support indicated potential control board and sensor failures on both indoor units but could not definitively diagnose without further testing due to code clearing after reset. Advised homeowner to operate units on high fan speed during cooling mode to optimize performance. No definitive fault isolated at time of service; recommend monitoring system operation and potential replacement of indoor unit control boards and temperature sensors if issues persist.
Responded to a no-heat call on a commercial tanked water heater displaying a "Flame not detected" error message. Upon diagnosis, determined the igniter control module, igniter assembly, and spark ignition cable had failed. Replaced the defective igniter control, spark igniter assembly (AO Smith part #100271888), and spark ignition cable (AO Smith part #100271890) to restore proper ignition sequence and return the unit to full operational status.
Responded to callback for no cooling condition on 10+ year old system. Unit continued tripping on same fault code as previous visit. Performed diagnostic testing on electrical components and control board. Found system was being locked out by customer's peak control device, which was cycling the equipment off every few minutes. Reset system and monitored operation to confirm peak control interference was causing the repeated shutdowns. Educated customer on peak control program impact on system operation.
Responded to no cooling complaint on 10+ year old central air conditioning system with warm air from vents. Found outdoor unit failed to start due to high-pressure safety trip. Reset high-pressure switch by disconnecting wires from control board, allowing equipment to restart successfully. Monitored system operation for 25 minutes to verify proper function. Observed suction pressure reading slightly low but confirmed adequate cooling performance with 20-degree temperature split across evaporator coil. Evaporator coil showed proper refrigerant distribution with condensation forming along entire coil surface. Inspected outdoor condenser coil and confirmed clean condition with no obstructions or debris. Unable to identify specific cause of high-pressure trip as all components appeared to be functioning within normal parameters. Reset defrost board to restore system to factory settings. System operating properly at time of departure with no further issues detected.
Completed comprehensive multi-fixture plumbing service addressing several bathroom and kitchen issues. Installed customer-supplied kitchen faucet and sink strainers, replaced leaking shower cartridge in basement stand-up shower, and installed customer-supplied toilet in bathroom. Additionally, replaced internal flush valve components in downstairs bathroom toilet to restore proper function. All customer-supplied parts and fixtures were installed to manufacturer specifications and tested for proper operation and leak-free performance.
Completed annual air conditioning tuneup and preventative maintenance on Amana outdoor condenser unit and Lennox furnace system. Performed comprehensive inspection of all routine components including electrical connections, refrigerant levels, condensate drainage system, and airflow. All equipment tested and verified to be operating within normal parameters with no deficiencies noted.
Responded to no cooling call on 10-year-old Lennox central air conditioning system with outdoor unit not running and no airflow at registers. Diagnosed failed start capacitor on condensing unit preventing compressor operation. Replaced defective start capacitor with OEM equivalent and monitored full system operation through complete cooling cycle to verify proper compressor startup, airflow delivery, and temperature differential across evaporator coil.
Responded to service call for slow-draining bathroom sink. Successfully cleared clog located in the trap and pop-up assembly using appropriate drain cleaning tools. Sink now drains properly at normal flow rate.
©2026 Hurlburt. All Rights Reserved.
Privacy Policy | Terms and
Conditions
This site is protected by reCAPTCHA and the Google Privacy Policy and Google Terms of Service apply.