with Purchase of Furnace & AC
Includes Merv 16 5" media cabinent and ApcoX Premium UV-light. Cannot be combined with any other offers. Must present coupon at time of service. Not valid on previously completed work.
Our company provides heating services for furnaces, boilers, and heat pumps. We can also help you protect and enhance your indoor air quality in Mondovi, WI.
Our cooling technicians handle everything from energy-efficient upgrades to precision AC repair in Mondovi, WI. We even have technicians on call for emergency HVAC solutions throughout Mondovi.
We encourage area homeowners to schedule annual plumbing inspections. Our plumbers in Mondovi, WI can identify and correct issues before they get expensive.
We also offer reverse osmosis (RO) systems for households that want cleaner, better-tasting water.
We can help you modernize your home through our electrical services. That includes making it safer and more energy-efficient.
Our team provides cooling and heating repair throughout Mondovi, WI. We provide energy-efficient HVAC solutions that help residents significantly lower their heating bills. Those include high-efficiency furnaces, high-efficiency boilers, and dual-fuel heat pumps. This is an area with many older houses that have electrical systems dating back decades.
Our electricians in Mondovi, WI can upgrade them with new wiring, higher-amp electrical panels, and whole-house surge protection. Our plumbers in Mondovi, WI can help protect your home from the area’s hard water. That can improve water heater efficiency and the lifespan of your major appliances. Poor indoor air quality is a growing health concern, as local winters force people indoors for long periods. We can help you improve your air through air purifiers, humidity control, germicidal lights, and more.
Our family business is proud to serve Mondovi and the surrounding areas. We have over 65 years of experience and have earned more than 6,000 5-star customer reviews. Our team includes certified HVAC technicians, licensed plumbers, and licensed electricians in Mondovi, WI. For installations, we offer free quotes and financing on approved credit. Contact us anytime for emergency HVAC services in Mondovi. We offer same-day appointments and have a live answering service on call 24/7. For maintenance, explore our Hurlburt Family Rewards program. Membership can save you money while making HVAC, plumbing, and electrical maintenance more convenient.
Hurlburt is a local, trusted choice for plumbing, electrical, and HVAC services in Mondovi, WI. We carry that genuine Midwestern hometown care into every house we step into, backed by the skill and equipment to deliver top-tier results. We work with homeowners to help them choose options that will work for them and their households. To schedule an appointment, call today or book online.
Responded to No Heat call for second property where furnace displayed ignition lockout alarm. Diagnostic testing revealed gas valve was providing insufficient flow, causing only one burner to ignite and resulting in failed ignition sequence. Observed inducer motor exhibiting noise upon startup that subsided during operation. Replaced defective gas valve to restore proper heating function and left temporary space heaters while awaiting parts.
Responded to a heat pump short cycling complaint. Performed system diagnostics and monitored operation for 30 minutes; confirmed proper functionality with no error codes and verified a 24° temperature split. Checked humidifier operation which was maintaining proper humidity levels (41% with thermostat set at 40%). Ran full test cycle with no issues detected. All systems operating within normal parameters.
Removed and replaced old sediment filter with new 20" Point of Entry Sediment Filter Kit. Cut existing piping and installed new sediment filter system, properly connecting it to the home's water treatment setup which includes existing water softener components and pressure tank.
Performed scheduled maintenance on IBC boiler as part of Family Rewards agreement. Conducted comprehensive inspection with no issues detected. System is operating properly with all components in good working condition.
Performed annual LP furnace maintenance inspection and identified multiple cracks in the heat exchanger along with holes in the side wall, documented with detailed photos of the metal degradation and staining. Due to the compromised heat exchanger integrity, replacement of the furnace is recommended, with pricing information to follow.
Diagnosed Amana 90 high-efficiency furnace (Model #GUD070X30B) with no heat complaint. Inspection revealed failure of power transmission to ignitor due to defective control board. Provided customer with replacement board options and discussed potential full furnace replacement alternatives.
Performed comprehensive FRP furnace tune-up on aging Lennox system, replacing customer-supplied dirty filter. Identified blower with slight play and faulty capacitor (7.5uf cap reading 5.9uf). All other electrical components within specification. Heat exchanger inspection revealed concerning areas developing but currently no compromises. System operated properly with 45-degree temperature rise and correct gas pressure. Recommended blower motor and capacitor replacement, with customer agreeing to pricing consultation for potential system upgrade due to age and condition.
Completed diagnostics on chapel furnaces that were not functioning properly. Identified air flow issues between units causing filter displacement and inadequate heating. Pulled and cleaned burners per customer request; however, new burners are still required. Examined heat exchangers and verified system operation.
Responded to no heat call for furnace not maintaining temperature. Diagnosed condensate system blockage caused by beetle infestation. Removed and flushed condensate boot and drain line, clearing all obstructions. Inspected heat exchanger for cracks/holes with none found. Verified proper system operation after service with furnace functioning normally.
Responded to customer complaint regarding thermostat issues reportedly limiting temperature to 64 degrees. Upon arrival, found interior temperature at 78°F with thermostat reading 80°F, contradicting the reported issue. Performed visual inspection of the Westcap furnace system installed in March 2024 and found no operational issues or wiring problems. Recommended customer contact original installation contractor as system appears to be functioning correctly and is under recent installation warranty.
Diagnosed and repaired 15-year-old furnace with no heat due to a weak pilot flame causing flame sensing failure. Removed pilot assembly, cleared obstruction in gas tubing, and reinstalled components, successfully restoring proper ignition and operation. Noted significant dust accumulation in blower motor requiring cleaning or replacement and recommended new pilot assembly for future reliability.
Applied professional-grade silicone caulking around newly installed kitchen sink to create proper water seal. Previous caulking was inadequate; completed high-quality application to ensure watertight junction between sink basin and marble countertop.
Responded to no-heat complaint on 9-year-old furnace that was failing to ignite and locked out on retries. Diagnosed issue with dirty burners, removed and cleaned burner assembly components to restore proper flame pattern. System was monitored through multiple cycles to confirm proper ignition and operation before leaving.
Performed a tune-up inspection on a 20-year-old Crown boiler system with underfloor heating. Identified one water circuit with a removed valve knob that was turned off, possibly due to prior leaking issues. Due to unfamiliarity with this specific older unit, recommended a follow-up visit from a specialized boiler technician for further evaluation.
Responded to no-heat call for 13-year-old boiler system with intermittent operation issues. Diagnostic testing revealed gas valve faults on both boilers, which were short cycling and losing flame signal during low modulation. Inspection of the more problematic unit showed severely plugged heat exchanger and damaged burner door gasket. Recommended boiler tune-up and Ultra maintenance with gasket kit. Left problematic boiler disabled due to safety concerns from missing gasket components and potential flue gas leakage. Customer requested email estimates before proceeding with repairs.
Responded to no-heat call for a furnace with pilot light ignition but non-functioning main burners. Diagnosed low continuity in flame sensor and performed cleaning with Scotch-Brite. While cleaning provided temporary improvement, advised customer about age and condition of furnace, noting this was a temporary solution. System uses Honeywell ProSeries thermostat and Smart Valve 6-1 control.
Responded to no-heat call on aging furnace. Diagnosed failed igniter with visible crack upon removal. Replaced igniter successfully restoring heat function. Noted inducer motor showing early failure signs with excessive shaft play - recommended monitoring and future replacement.
Completed a 2-hour repair service involving the replacement of an AMTROL expansion tank and rebuild of a zone valve in customer's basement heating system. After installation, system was properly bled of air and tested for proper circulation. Both zones now functioning correctly with heat distribution verified throughout.
Diagnosed toilet leaking from base to lower level. Found loose toilet bolt causing seal failure. Reset toilet with new wax ring, tightened mounting bolts, and installed new cap set. Replaced toilet supply line to complete repair.
Performed fall maintenance tune-up on 5-year-old Tempstar furnace system. Conducted comprehensive inspection with all components checking out properly. System functioning normally with no issues identified. Discussed maintenance plan options with homeowner for future service consideration.