Since 1959 Hurlburt, we make it our mission to keep your home comfortable and protected.
with Purchase of Furnace & AC
Includes Merv 16 5" media cabinent and ApcoX Premium UV-light. Cannot be combined with any other offers. Must present coupon at time of service. Not valid on previously completed work.
The winter weather in Chippewa Falls makes it essential to have a dependable heating system because temperatures drop brutally low. When something goes wrong, you don’t want to risk damaging the system or injuring yourself with a DIY heating repair in Chippewa Falls. Instead, you need to call Hurlburt. We’ll send a trained technician to find and fix the underlying problem so that you don’t have to go without heat.
We’ll design a cooling system that perfectly matches your needs. This may look like a central setup with ductwork or a ductless mini-split using heat pump technology. The home’s square footage and layout impact choosing the right equipment. When something goes wrong, we’re just a phone call away. We’ll send a technician to implement a lasting solution that keeps the home cool and energy-efficient.
Our plumbers in Chippewa Falls, WI install water heaters, repair sump pumps, clear clogged drains and more. Emergency plumbing service is available for water leaks and burst pipes. We’re experts at finding and fixing hidden leaks beneath floors and behind walls.
You don’t want to ignore leaks and burst pipes because they increase the risk of water damage. Moisture buildup can lead to mold growth that causes respiratory and structural problems. Our solutions for leaks and burst pipes include pipe repairs, repiping and installing new shut-off valves. We’ll consider the leak’s location and severity to choose the best option.
Do you need to procure an EV charger upgrade? Hurlburt wants to help. We’ll match the charger to your charging needs and electrical system. Some homes require upgrades to their wiring to ensure compatibility with an EV charger. Some also require the installation of a dedicated circuit to feed the charging station. We’ll do a thorough inspection to see which upgrades your home needs.
We offer support for whole-home generators, smart home devices and other major electrical projects, too. We can even completely rewire your home. For example, if you’re still using outdated knob-and-tube wiring, we can upgrade it with modern grounded wiring. This makes the home safer by reducing the risk of electrical fires.
We’re the company that folks call when they need emergency HVAC in Chippewa Falls. We’ve helped numerous customers with furnace replacements after unexpected breakdowns. We’re also a trusted resource for achieving better indoor air quality in Chippewa Falls, WI. The humidity swings and seasonal allergens here contribute to stale, uncomfortable indoor air. With a whole-home air purifier in place, it becomes much easier to breathe easier and stay comfortable year-round.
We offer same-day service for emergency issues that need immediate attention, like burst pipes and refrigerant leaks. The technician who comes to your home will have gone through training and background checks. All HVAC installations we perform follow precise load calculations because we care about lasting performance.
Hurlburt isn’t your average home services company. We’re an all-in-one provider of electrical, HVAC and plumbing work. You won’t have to juggle multiple contractors just to get repairs or new installations. Homeowners frequently call us for heating and electrical upgrades. We love syncing thermostats and lighting with smart home systems to achieve better comfort and optimal energy efficiency.
Joining the Hurlburt Family Rewards Club gives you an easy way to save money on future repairs. Contact Hurlburt now to access professional solutions for plumbing, electrical, or HVAC in Chippewa Falls, WI.
Responded to routine AC tune-up maintenance call on 24-year-old Lennox system. Upon arrival, found indoor blower operational but outdoor condensing unit not engaging. Inspection revealed severely pitted contactor with insect debris causing failure, and condenser fan motor showing signs of increased resistance. All other electrical components tested within acceptable parameters. Verified evaporator coil, blower assembly, and condensate drain line all clean and functioning properly; air filter in good condition. Cleared debris from contactor to restore temporary operation of outdoor unit. Conducted 15-minute system performance test, confirming 15-16°F temperature split across evaporator coil. Measured operating pressures and identified low refrigerant charge on R22 system, indicating potential leak. All ductwork and indoor components found in satisfactory condition. Given age of equipment, deteriorating contactor condition, stiffening fan motor, and low refrigerant levels, advised that
Upgraded thermostat from S30 model to S40 model. Upon initial installation, the new thermostat failed to recognize the air conditioning system, indicating a communication issue. Diagnosed the problem as faulty or inadequate wiring between the thermostat and HVAC equipment. Ran new control wire from thermostat location to air handler, terminated all connections properly, and verified system operation. System now functioning correctly with full thermostat control of both heating and cooling modes.
Performed routine cooling maintenance on heat pump system. Upon arrival, inspected air filter and blower assembly, both found in satisfactory condition. Identified evaporator coil drainage issue with improper pitch causing water to drain away from drain line. Discovered mouse nest in outdoor unit electrical panel with deceased rodent on run capacitor, causing hermetic compressor circuit failure. Measured capacitor at 4.5uf, significantly below 35uf specification. Cleaned condenser coil and verified all other system components within manufacturer specifications. Repositioned evaporator coil in attic by lifting and tilting unit to improve drainage slope. Disconnected return air section and installed support pad underneath to maintain proper pitch. Replaced failed 35uf run capacitor with new component. Conducted operational test with 15-minute runtime to verify proper system function. All parameters normal, cooling cycle operating as designed. System restored to full operational capacit
Performed comprehensive AC tune-up on residential split system. Inspected and confirmed air filter, blower assembly, and evaporator coil were clean with proper drainage. Verified all electrical components operating within manufacturer specifications. Cleaned condenser coil, tested system operation for 15 minutes, and confirmed proper cooling with 19-20 degree temperature differential across the coil. Left replacement filter on-site. System operating normally with no issues found.
Responded to emergency call for active water heater leak causing water damage to surrounding floor area. Upon inspection, identified leak originating from bottom jacket of existing tanked water heater, indicating tank failure and requiring immediate replacement. Removed failed water heater unit and installed new tanked water heater in utility closet alongside existing water treatment equipment including water softener and well pressure tank system. Connected all supply and discharge plumbing lines, verified proper venting through existing metallic duct system, and tested unit operation to ensure proper heating function and confirmed no leaks at connections. Placed dehumidifier in area to assist with drying from previous water damage.
Completed comprehensive AC tune-up on residential system. Found outdoor condenser coil completely plugged with debris, performed thorough coil cleaning to restore proper airflow and heat transfer. Verified system operation with 14° temperature split at 800 CFM airflow, which is within acceptable parameters. Noted Y2 terminal not jumpered at unit with only two-wire thermostat connection present—system has operated satisfactorily for four years in current configuration, so no modifications were made to avoid potential issues during peak cooling season. Completed all standard maintenance procedures and confirmed proper system operation.
Performed comprehensive air conditioning maintenance on a 2020 Carrier single-stage R-410A system with TXV metering. Verified system operation with indoor temperature differential at 19°F and measured subcooling consistently between 7.8°F–8.0°F against nameplate target of 10°F, confirming acceptable performance. Inspected and tested original run capacitor, which remains within manufacturer specifications. Identified outdoor disconnect as degraded plastic type showing UV damage and material deterioration, presenting potential reliability and safety concerns; recommended replacement for improved system safety and longevity.
Responded to service call for shower faucet handle malfunction. Upon inspection, diagnosed faulty cartridge as the source of the operational issue. Provided estimate for cartridge replacement, but customer declined repair service at this time.
Performed comprehensive AC maintenance and pre-maintenance evaluation on a 2022 Nordyne furnace and air conditioning system in response to complaints of extended run times and inadequate cooling performance. Conducted thorough inspection of system components, verified blower airflow settings, and tested operation with both existing and new air filter to isolate potential airflow restrictions. Utilized Bluon diagnostic application to analyze system performance metrics, which confirmed an apparent refrigerant undercharge condition consistent with reported cooling deficiencies. Documented system specifications including model WSA2BD4M1SN30K with electrical ratings of 208/230V and 30A overcurrent protection. Photographed heat exchanger condition showing minor discoloration and captured unit nameplate data for service records. Provided detailed repair recommendations and pricing options to address the identified low refrigerant charge issue requiring further diagnostic work and potential le
Responded to shower/tub drain issue with waste water odor concerns. Upon inspection, determined that installing a trap in the proposed location would not resolve the problem and would violate plumbing code requirements. Assessed the existing drain configuration and identified inadequate pipe sizing and lack of proper venting as root causes of the odor issue. Provided estimate for compliant repair solution including increasing pipe diameter, opening drywall section to install code-compliant trap beneath shower pan, and adding proper vent stack to eliminate sewer gas infiltration. Additionally identified non-compliant washing machine drain line installation and provided separate estimate for bringing system up to code standards.
Responded to no cooling complaint on 8-year-old central air conditioning system. Upon arrival, performed system diagnostics and discovered furnace disconnect switch in OFF position. Customer had been organizing basement area and inadvertently turned off power switch at furnace. Restored power by switching disconnect to ON position, and system immediately resumed normal cooling operation. Verified proper system startup, confirmed adequate airflow, and ensured compressor and condenser unit were functioning correctly with no further issues present.
Performed comprehensive AC maintenance on one R-410A condensing unit with no reported issues. Conducted full system inspection including air filter, Honeywell thermostat operation, temperature split measurements, condenser coil condition, evaporator coil, blower motor, capacitor testing with multimeter, compressor amperage draw, refrigerant charge level, and condensate drain line. All components tested within normal operating parameters at 65-degree ambient temperature, and system is cooling properly.
Performed annual AC tune-up on Lennox system per maintenance agreement. Washed outdoor condenser unit, tested all electrical components confirming proper voltage and amperage within manufacturer specifications, and verified 20-degree temperature split across evaporator coil. Inspected air filter which remains in serviceable condition but will require replacement prior to heating season.
Completed comprehensive plumbing inspection as part of friends and family service program. Inspected all accessible plumbing fixtures and components including bathroom sink with dual-handle chrome faucet, water heater supply valves with braided flex lines, and shut-off valve assemblies. All fixtures confirmed operational with no leaks, drainage issues, or functional concerns reported. Minor surface corrosion noted on valve mounting hardware but does not affect operation. All systems verified in proper working order with no immediate repairs required.
Completed comprehensive plumbing inspection for friends and family service call. Evaluated existing Mansfield builder-grade toilets throughout the residence and assessed current Delta faucet installations in kitchen and bathrooms for potential whole-house upgrade. Referred customer to supplier for fixture selection, with plans to replace all faucets pending customer's final choices. Documented kitchen sink configuration featuring stainless steel double-basin setup with single-handle faucet. Coordinated inspection with scheduled HVAC service for comprehensive property assessment.
Completed comprehensive AC maintenance on one 3-year-old condenser unit utilizing R-410A refrigerant under 60-degree ambient conditions. Performed full system inspection including filter evaluation, thermostat operation verification, temperature split measurement, condenser and coil examination, motor and capacitor testing, compressor assessment, refrigerant level check, and condensate drain inspection. Accessed interior electrical and control components, inspecting dual circuit boards, wiring connections, and all internal systems. Noted minor debris accumulation on exterior coil fins but system demonstrated normal operational parameters across all tested components with no deficiencies requiring immediate attention.
Responded to no cooling callback on 11-year-old R-410A system that had refrigerant and UV dye added approximately one month prior. Found suction line frozen solid from evaporator outlet to compressor, indicating system is low on refrigerant again due to active leak. Shut down outdoor unit to prevent compressor damage and left indoor blower running to thaw evaporator coil. Contacted property owner by phone to explain situation. Previous refrigerant addition was temporary measure to restore operation and facilitate leak detection with UV dye. Recommended completing leak search using installed dye, repairing identified leak, evacuating system, and recharging to factory specifications, or replacing aging system.
Performed comprehensive tune-up on 1988 Trane XE 900 air conditioning unit with extensive dirt accumulation. Disassembled and thoroughly cleaned condenser coils and cabinet, tested all electrical components including contactor, and measured capacitor readings—fan capacitor within specifications, compressor capacitor reading 32/35 microfarads and recommended for replacement. Confirmed 18-degree temperature split and proper system operation upon completion.
Completed comprehensive plumbing inspection including water quality testing of the residential water heating and treatment system. Inspected water heater, water softener/filtration equipment, and associated piping connections in basement utility area, documenting conditions with photographs. Provided detailed estimate for recommended repairs identified during inspection.
Completed comprehensive BOGO tune-up service on residential AC and furnace system. Performed full inspection of outdoor condenser unit, thoroughly washed exterior cabinet and coils to remove accumulated dirt and debris, and verified all electrical components reading within manufacturer specifications. Inspected indoor furnace system, confirmed air filter in good condition, tested all electrical connections and readings within proper parameters, cleared condensate drain hoses, and cleaned flame sensor to ensure optimal ignition performance. Both heating and cooling systems operating properly with no deficiencies noted at time of service completion.